Compressed air is widely used in variety of manufacturing & measurement applications. Compressed air coming out of compressor is contaminated by moisture, oil and dust particles.
For efficient and effective use of compressed air it is necessary to remove these contaminants to acceptable level as per application.
Operation of Refrigeration dryer:
Wet compressed air enters Pre-filter where liquid droplets are separated and then enters in pre cooler (known as air to air cooler). Outgoing chilled air-cools incoming wet air in pre-cooler. Condensed moisture in pre cooler is separated in pre moisture separator. Precooled 100% saturated air enters in evaporator (also known as chiller) here it is cooled to dew point temperature of +3 deg or as per set point. Chilled air, while passing thro moisture separator, is stripped of all liquid moisture and removed by auto drain continuously. Chilled air is made to pass through air-to-air exchanger and is heated by incoming wet air.
Refrigeration unit uses eco friendly CFC (R134 A, R404 A), provides chiller outlet air temperature controller controls cooling for compressed air and operation.
"Guardian " Series Refrigerated Dryer
Model
Flow ** Nm3/hr
Flow Scfm
ConnectionSize
Control By
RAD 003
30
16
½" BSP (F)
HGBV
RAD 006
60
32
½" BSP (F)
HGBV
RAD 010
100
60
¾" BSP (F)
HGBV
RAD 018
174
100
1" BSP (F)
HGBV
RAD 026
260
150
1 ½" BSP (F)
HGBV
RAD 035
348
200
1 ½"BSP (F)
HGBV
RAD 045
440
250
2" NB
HGBV
RAD 053
521
300
2" NB
HGBV
RAD 069
695
400
2 ½" NB
HGBV
RAD 087
870
500
2 ½" NB
HGBV
RAD 104
1042
600
2 1/2" NB
AEV
RAD 130
1300
750
3" NB
AEV
RAD 156
1563
900
3" NB
AEV
RAD 174
1740
1000
4" NB
AEV
RAD 208
2084
1200
4" NB
AEV
RAD 347
3472
2000
6" NB
AEV
RAD 521
5210
3000
6" NB
AEV
HGBV Hot Gas Bypass Valve
AEV Automatic Expansion Valve
Inlet flow is calculated based on **
Reference conditions
Compressor Suction Pr
1.03 kg/cm2 ab
14.7 Psia
Suction Temp
40 Deg C
104 Deg F
RH
65%
65%
Pressure Dew point
(+) 3 deg C
37.4 Deg F
Atmospheric Pr Dew point
(-) 20 Deg C
(+) 4 Deg F
Inlet temperature
40 Deg C
104 Deg F
Inlet temperature Max.
60 Deg C
122 Deg F
Operating Pressure
7 Bar(g)
100 psig
Ambient Temperature
40 Deg C
104 Deg F
Ambient Temperature Max
45 Deg C
113 deg F
Supply Voltage 50 Hz
1 Phase 230 V
3 Phase 415 V
For other compressed air inlet conditions please
refer our office for multiplying factors for K1 pressure dew point K2 Inlet air temperature K3 Inlet air pressure K4 Ambient temperature
Qactual= Qnominal * K1 * K2 * K3 * K4
Due to continual improvement specifications are subjected to change with out notice. Rev .19/12/06